Summary :

To one double-breaker model, experimental investigation on blow open force was carried out. It demonstrates that the ratio between the emerging blow open force and arc power FB/ui decreases with the arcing time, the contact gap has less effect on FB/ui, and the characteristics of the blow open force are similar when the peak value of the short circuit current is beyond 4 kA. Then, according to the experimental data and conclusions, considering the influence of blow open force, the interruption process of molded case circuit breakers (MCCBs) was investigated. It demonstrates the blow open force has significant influence on interruption process and the proposed method is effective to evaluate new design of MCCBs.

Publication
IEICE TRANSACTIONS on Electronics Vol.E89-C No.8 pp.1187-1193
Publication Date
2006/08/01
Publicized
Online ISSN
1745-1353
DOI
10.1093/ietele/e89-c.8.1187
Type of Manuscript
Special Section PAPER (Special Section on Recent Development of Electromechanical Devices (Selected Papers from IS-EMD2005))
Category
Contactors & Circuit Breakers